HomeMy WebLinkAbout(100) Hydrant and Gate ValveCLOW
HYDRANT FLAG TO BE (MAX)
MEDALLION HYDRANT
INSTALL TO DETAILS
INSTALLED ON THE
SHOWN FOR WATEROUS
NOZZLE SECTION.
CLASSIC PACER
HYDRANT
2' (MIN) 2'
ONE PIECE OPERATING -EYP, TYP.
NUT WITH
WEATHERSHIELD
TYP• WATEROUS CLASSIC PACER
Q
19 3/8
MIN 21"
GROUNDLINE MAX 24" 2-3" BELOW
GROOVE GRADE
11
— I--� I—I I I—I I Wil I=III—III—III > -'
� =I � iii—iii—iii—iii—iii—iii i—iii—iii—iii—i : s• e e s
I-I
—III—III= �- � ' ■ � ��
UNDISTURBED—III—� 1 CU. YD. CLEAR
SOILS III—III— ROCK
��I I—III—I COVER W/ 2 LAYERS G.V. ADAPTER
—III—III— POLYETHYLENE (4MIL)
SEE CONCRETE
8' BURY6„ I III I II I I
THRUST BLOCK
STANDARD PLATE
—III-I I 6" DIP
I—III-I I
�H—III RESILIENT
-I I M.I
WEDGE VALVE
� •
O,a
I I=III— ``•e
°'',
-
8" CONCRETE III—= — •� •Q ' �_
THRUST BLOCK I—III=I _' _ _—
LWATERMAIN
8" CONCRETE III=I —= III—III—III—III—III= 8" CONCRETE
t li I I I=1 I I; I I1=1 I I-III
BLOCK -1 i i i� BLOCK
'
NOTES:
HYDRANTS SHALL BE EITHER CLOW MEDALLION OR WATEROUS CLASSIC PACER MODEL WB67-250 BOTH SHOULD HAVE
ONE (1)—FIVE AND ONE—QUARTER INCH (5 J") STORZ PUMPER NOZZLE NTH 16" BREAK OFF AND TWO (2)—TWO AND
ONE—HALF INCH (2 J") THREADED NOZZLES.
ALL HYDRANTS AND GATE VALVES SHALL HAVE MECHANICAL JOINT CONNECTIONS. ALL VALVES TO OPEN
COUNTER—CLOCKWISE
HYDRANTS TO CONFORM WITH DIMENSIONAL REQUIREMENTS FOR NONTHREADED CONNECTIONS IN ACCORDANCE WITH
NFPA 1963 STANDARDS FOR FIRE HOSE CONNECTIONS.
ALL BACKFILL SHALL BE PROPERLY COMPACTED.
2 CANDYCANE STYLE FLAGS PER HYDRANT (ONE INSTALLED, ONE TO EDINA PUBLIC WORKS).
A ONE—PIECE HEAVY DUTY OPERATING VALVE ROD IS REQUIRED ON HYDRANTS THAT ARE EXTENDED 24" OR MORE.
TOP \AEW
WHEN INSTALLING A HYDRANT ROD EXTENSION, THE NONBREAKABLE COUPLING SLEEVES GO ON THE BOTTOM AND THE
BREAKABLE SLEEVES GO ON THE TOP OF THE EXTENSION ROD.
FIRE HYDRANTS SHALL BE PAINTED RED AT THE FACTORY.
POLYWRAP ALL PIPE AND FITTINGS, MEGA LUG ALL FITTINGS, INCLUDE CORROSION PROTECTION AT EACH JOINT.
SIDE VIEW
ALL HYDRANTS SHALL BE INSTALLED WITH STORZ NOZZLE PERPENDICULAR TO ROADWAY.
GATE VALVE ADAPTOR:
WEEP HOLE TO REMAIN OPEN.
1/4" STEEL WITH
PROTECTIVE COATING.
1/2" RUBBER GASKET
INSTALLED BETWEEN GATE
VALVE AND ADAPTOR.
A,Mi CITY OF EDINA
REVISED:
ENGINEERING
HYDRANT AND GATE VALVE
01-16
e
°I �o & PUBLIC
STANDARD
�\ �y WORKS
PLATE
DEPTS.
ZML
APPROVED: CITY ENGINEER
100