HomeMy WebLinkAbout(301) Sewer and Water Service Connection with RiserVARIES (SEE PLAN)
VARIES (SEE PLAN)
STEEL FENCE POST J
7.5' MIN.
CURB BOX SHALL BE MUELLER
H-10300 MINNEAPOLIS PATTERN
1 1/4" STACK FOR USE WITH 1"
CURB STOP.
1" CURB STOP SHALL BE
MUELLER H-15154 MINNEAPOLIS
PATTERN OR APPROVED EQUAL
ALL STOPS SHALL BE FLARED FOR
BOTH INLET & OUTLET.
I
1'
l
~ 2"x2" .... MARKER
t
Ffn
~
0::
LI.I
0.. !!;; 0..
LI.I:::> 0 c8 0::
0..
:Z 0::
WATER MAIN_/
WATER SERVICE
CONCRETE BRICK
CORPORATION STOP SHALL BE MUELLER
H-15000 OR APPROVED EQUAL WITH MUELLER
THREAD FLARE TYPE JOINT.
!$! -Ul ::::ii< 0::
LI.I bo:: Ul
T'""Q ~
CITY OF EDINA
ENGINEERING
& PUBLIC
WORKS
DEPTS.
MIN SLOPE 1/4"
PER FT. (2.0%)
STUB
ELEV.
4" OR 6" PVC SOR 26
SEWER SERVICE PIPE.
SANITARY SERVICE WYE
TURNED UP AT A 45'
SANITARY SEWER
MQIE.S.:_
ANY CURB STOP LOCATED IN BLACKTOP OR CONCRETE DRIVEWAY
OR SIDEWALK SHALL BE COVERED WITH METER BOX COVER
(FORD A-1) OR APPROVED EQUAL
ALL WATER SERVICES SHALL BE 1" MIN., TYPE K COPPER, AND
SHALL USE A SMITH BLAIR STAINLESS STEEL SADDLE TYPE #317 OR
#372, OR APPROVED EQUAL
WATER SERVICE MUST BE CONTINUOUS WITH NO JOINTS UNLESS
SERVICE IS OVER 100' LONG.
SANITARY AND WATER SERVICE LINES SHALL BE INSTALLED IN THE
SAME TRENCH WITH 3' OF SEPARATION.
EXCESSIVE SANITARY SEWER MAIN-LINE DEPTH SHALL BE REVIEWED
AND APPROVED BY THE ENGINEER.
SANITARY SEWER SERVICE RISER SHALL BE BACKFILLED WITH
GRANULAR MATERIAL AND COMPACTED.
SEWER AND WATER SERVICE REVISED:
01-17
APPROVED: CITY ENGINEER