HomeMy WebLinkAbout(100) Hydrant and Gate ValveHYDRANT FLAG TO BE
INSTALLED ON THE
NOZZLE SECTION.
ONE PIECE OPERATING
NUT WITH
WEATHERSHIELD
TYP.
SME VIEW
GATE VALVE ADAPTOR:
1/4" STEEL WITH
PROTECTIVE COATING.
1/2" RUBBER GASKET
INSTALLED BETWEEN GATE
VALVE AND ADAPTOR. GROUNDUNE
GROOVE
UNDISTURBED .1_
SOILS 1-=-111-=1
6"
- 1 CU. YD. CLEAR
ROCK
COVER WI 2 LAYERS
POLYETHYLENE (4MIL) SEE CONCRETE
THRUST BLOCK
STANDARD PLATE
Er CONCRETE
THRUST BLOCK
6" CONCRETE
BLOCK 11_111_ III-II I
8" CONCRETE m BLOCK
WATERMAIN
10'
(MAX)
0
8' BURY
NOTES:
HYDRANTS SHALL BE WATEROUS CLASSIC PACER MODEL WB67-25O WITH ONE (1)-FIVE AND ONE-QUARTER INCH (5 STORZ PUMPER
NOZZLE WITH 16" BREAK OFF AND TWO (2)-TWO AND ONE-HALF INCH (2 t) THREADED NOZZLES.
ALL HYDRANTS AND GATE VALVES SHALL HAVE RESTRAINT COUPLING, RESTRAINT JOINT OR MECHANICAL JOINT CONNECTIONS. ALL VALVES TO
OPEN COUNTER-CLOCKWISE.
HYDRANTS TO CONFORM WITH DIMENSIONAL REQUIREMENTS FOR NONTHREADED CONNECTIONS IN ACCORDANCE WITH NFPA 1963 STANDARDS FOR
FIRE HOSE CONNECTIONS.
ALL BACKFILL SHALL BE PROPERLY COMPACTED.
2 CANDYCANE STYLE FLAGS PER HYDRANT (ONE INSTALLED, ONE TO EDINA PUBLIC WORKS).
A ONE-PIECE HEAVY DUTY OPERATING VALVE ROD IS REQUIRED ON HYDRANTS THAT ARE EXTENDED 24" OR MORE.
MEN INSTALLING A HYDRANT ROD EXTENSION, THE NONBREAKABLE COUPLING SLEEVES GO ON THE BOTTOM AND THE BREAKABLE SLEEVES GO
ON THE TOP OF THE EXTENSION ROD.
FIRE HYDRANTS SHALL BE PAINTED RED AT THE FACTORY.
POLYWRAP ALL PIPE AND FITTINGS, MEGA LUG ALL FITTINGS, INCLUDE CORROSION PROTECTION AT EACH JOINT.
ALL HYDRANTS SHALL BE INSTALLED WITH STORZ NOZZLE PERPENDICULAR TO ROADWAY.
WEEP HOLE TO REMAIN OPEN.
CITY OF EDINA
ENGINEERING
& PUBLIC
WORKS
DEPTS.
HYDRANT AND GATE VALVE
REVISED:
1-19
STANDARD
PLATE
100
Si/ le
APPROVED: CITY ENGINEER